Trigger Action E-Stop
Environmental ratings (actuator)
Ingress protection UL (NEMA) 1, 2, 3, 3R, 4, 4X, 12 & 13 and IEC IP 65 when mounted on a .at surface of a similarly rated enclosure. Above ratings do not apply to applications where devices are mounted directly unto a machine without the use of a separate console or enclosure. If not installed in a suitable panel or enclosure, precautions must be taken to safeguard contact blocks against electrical contact or shock and from contamination from environmental or working conditions of the machine.
Operating temperature –20° to +60°C
Storage temperature –40° to +80°C
Altitude 2,000m
Humidity Max 95% RH @ 60°C
Flammability UL94 V-O rated
UV resistance Shield actuator from excessive exposure to UV, and routinely perform a functional test of the emergency stop switch and inspect actuator for fading and cracking after every 500 hours of UV exposure.
Mechanical endurance ratings (actuator)
Life 100,000 cycles (actuation & release)
Frequency of operation 6 per minute
Vibration 5g, 0.7mm peak to peak, 10 sweeps, 10 to 500Hz
Shock 30g, 12ms
Bump 25g, 6ms for 1,000 cycles
Electrical ratings (contact blocks)
A600 & Q600 per UL508
AC15 & DC13 per IEC 60947-5-1
AC Life (AC15) 120Vac, 6A - 1,000k operations
DC Life (DC13) 24Vdc, 4A - 400k operations
N.C. Contacts DOA (direct opening action) per IEC 60947-5-1
Short circuit co-ordination rating 1kA
Short circuit co-ordination fuse GE Power Controls TIA 10, Red Spot type gG, 10A 660Vac 460Vdc, BS88-2, per IEC 60269-2-1
Standards & certifications
UL Listed E-Stop device per file # E217948
Certified to EN 60947-5-1 & EN 60947-5-5 per DEMKO certificate # 129648-01/A1
Certified to EN418 per DEMKO Certificate # 129648-02/A2
UL508 listed per file # E131568
CSA certified per file # LR68551

 

 