Voltage Test |
| Voltage Range |
12~690V AC/DC |
| Nominal Voltage |
12/24/50/120/230/400/690V
AC(45~400Hz), DC(±) |
Tolerance
(Threshold Voltage) |
Light on at more than:
7±3V (12V LED)
18±3V (24V LED)
37.5±4V (50V LED)
75%±5% of nominal voltage
(120/230/400/690V LED) |
| Response Time |
<0.5s at 100% of each nominal voltage |
| Peak Current |
ls<3.5mA (at 690V) |
| Internal Battery Consumption |
Approx. 33mA (battery 3V, measuring
690V AC) |
| Battery Life |
Approx. 2500 operations (30s ON/240s
OFF duty) |
|
Single-Pole Phase Test |
| Voltage Range |
100~690V AC (45~100Hz)
180~690V AC (100~400Hz) |
|
Phase Rotation Test |
| System |
Three-phase 4-wire system
200~690V phase-to-phase
(100~400V earth-to-phase)
AC 50/60Hz |
| Phase Range |
120±5 degree |
|
Continuity Test |
| Detection Range |
0~400kΩ+50% |
| Test Current |
Approx. 1.5μA (battery 3V, 0Ω) |
| Internal Battery Consumption |
Approx. 30mA (battery 3V, 0Ω) |
|
General |
| Operating temperature and humidity
ranges |
-10~55ºC, max 85% RH
(no condensation) |
| Storage temperature and humidity
ranges |
-20~60ºC, max 85% RH
(no condensation) |
| Applicable Standard |
IEC61010-1 CAT.III / IV 600V
IEC61243-3 CAT.II 690V
Pollution degree 2 |
| IP Rating |
IP65 (IEC60529) |
| Power Source |
LR03 1.5V×2 (3V) |
| Dimensions |
241.5(L)×68.5(W)×28.5(D) mm |
| Weight |
230g (including batteries) |