When load current is not affected by the distortion, both
averaging value type and true RMS (root mean square) type clamp
meters show the almost same value of about 10A with constant
wave-form as the above display samples. However, when load
current is affected by some distortions such as inverter,
etc...,averaging value type clamp meter indicates 5.5A instead
of 9.7A and true RMS type clamp meter indicates 7.9A instead of
9.7A with irregular wave-form. Accordingly, true RMS type clamp
meter is recommendable for the measurement of the equipment with
inverter control devices.
Due to the use of thyristors, inverters and other
energy-saving controllers in recent electric wiring, current
waveforms often include harmonic components and are distorted
compared to sinusoidal waves (50/60Hz).
The Kyoritsu True RMS value tester is able to measure distorted
waveforms using true RMS since waveforms are being internally
calculated continuously. In contrast, when measurements are made
with a averaging value tester, errors are generated in the
measurement value because the tester cannot continuously track
distorted waveforms.
(Compared to the true RMS value tester, measurement values for
the averaging value generate more than 30% errors in some
cases.)
|
Range |
Measuring Range |
Accuracy |
| Current
Measurement |
AC A 0 to 100.0A |
|±2.0%rdg±5dgt (50/60Hz) |
|
DC A 0 to ±100.0A |
|±2.0%rdg±5dgt |
| Conductor Size |
Max Ø10mm |
| Non Contact Voltage |
Detect AC voltage
without contacting with socket wire |
During voltage detection,
"Hi" flashes and
a buzzer sounds intermittently |
| Dimensions |
161.3(L) × 40.2(W) ×
30.3(D)mm |
| Crest Factor |
2.5 |
| Weight |
110g (with batteries) |
| Maximum Digit |
1,049 |
| Safety Standard |
IEC 61010-1 CAT.III 300V
Pollution Degree 2 |
| Power Source |
R03 (AAA) × 2 |
| Accessories |
Carrying Case
R03 (AAA) × 2
Instruction Manual |
| |
|
|
|