| DC Test Voltage |
1k~10kV variable |
1000V |
Measuring Ranges
(automatic change) |
1.6GΩ/100GΩ
(autoranging) |
100MΩ |
First
Effective
Measuring Ranges
Accuracy |
0.05~50GΩ |
1~100MΩ |
| |±10% rdg |
| Other ranges Accuracy |
|±1% of scale length |
Output Voltage and
Set Voltage Indicate |
ADC 0~10kV
|±2%rdg±2dgt |
| Withstand Voltage |
5000V AC for 1 minute |
| Power Source |
Ni-Cd rechargeable
battery(1.2V) × 8 |
| Dimensions |
200(L) × 140(W) × 80(D)mm |
| Weight |
1.5kg approx. |
| Accessories |
082(Lead for recorder)
7083(Lead for battery charging)
7084(Earth and guard leads)
8079(120V) or 8080(220V) (Battery charger)
9112(Hard Carrying Case)
Ni-Cd rechargeable battery × 8
Instruction Manual |