MODEL |
3321A |
3322A |
3323A |
|
Insulation Resistance |
| DC Test Voltage |
250V/500V/1000V |
125V/250V/500V |
25V/50V/100V |
| Measuring Range |
50MΩ/100MΩ/2000MΩ |
20MΩ/50MΩ/100MΩ |
10MΩ/10MΩ/20MΩ |
| Mid-Scale Value |
1MΩ/2MΩ/50MΩ |
0.5MΩ/1MΩ/2MΩ |
0.2MΩ/0.2MΩ/0.5MΩ |
First Effective
Measuring Range
Accuracy |
0.05~20MΩ(250V)
0.1~50MΩ(500V)
2~1000MΩ(1000V) |
0.02~10MΩ(125V)
0.05~20MΩ(250V)
0.1~50MΩ(500V) |
0.01~5MΩ(25V)
0.01~5MΩ(50V)
0.02~10MΩ(100V) |
| |±5% of Indicated Value |
Second Effective
Measuring Range
Accuracy |
20~50MΩ(250V)
50~100MΩ(500V)
1000~2000MΩ(1000V) |
10~20MΩ(125V)
20~50MΩ(250V)
50~100MΩ(500V) |
5~10MΩ(25V)
5~10MΩ(50V)
10~20MΩ(100V) |
| |±10% of Indicated Value |
| AC Voltage |
600V |
| Accuracy |
|±3% of Full Scale Value |
| Safety Standard |
IEC/EN 61010-1 CAT.III
600V,CAT.II 1000V |
| Withstand Voltage |
5550V AC for 1 minute |
| Power Source |
R6P(AA)(1.5V) × 6 |
| Dimensions |
105(L) × 158(W) × 70(D)mm |
| Weight |
520g approx. |
| Accessories |
7103(Test Lead with Remote
Control Switch)
Pouch for Test Leads
Shoulder Strap
7081(Guard Connection Lead): 3321A only
8017(Extension Prod)
R6P(AA) × 6
Instruction Manual |
| Optional |
7115(Extension Probe)
8016(Pickel Type Prod)
9089(Carrying Case) |