MODEL |
4116A |
4118A |
| Loop Impedance Ranges |
20/200/2000Ω |
20/200/2000Ω |
Loop Impedance
Accuracy |
|±2%rdg±4dgtConsider accuracy of Loop
impedance |
|±2%rdg±4dgt |
| AC Test Current |
20Ω 25A
200Ω 2.3A
2000Ω 15mA |
20Ω 25A
200Ω 2.3A
2000Ω 15mA |
| AC Test Period |
20Ω (20ms)
200Ω (40ms)
2000Ω (280ms) |
20Ω (20ms)
200Ω (40ms)
2000Ω (280ms) |
| PSC Ranges |
|
200A(2.3A 40ms)
2000A(25A 20ms)
20kA(25A 20ms) |
| PSC Ranges Accuracy |
|
Consider accuracy of Loop impedance |
| Voltage |
110V-260V ±2%rdg±4dgt |
| Operating Voltage |
230V+10%
-15%(195V~253V)50Hz |
| Safety Standard |
IEC61010-1 CAT.III 300V
IEC61557-1,-3
IEC61010-2-031 Pollution Degree 2 |
| IP Rating |
IEC60529-IP54 |
| Dimensions |
185(L) × 167(W) × 89(D)mm |
| Weight |
750g approx. |
| Accessories |
Molded plug test leads
Pouch for test leads
Shoulder Strap
Instruction Manual |
Molded plug test leads
7121
(Distribution board test leads)
Pouch for test leads
Shoulder Strap
Instruction Manual |
| Optional |
7121
(Distribution board test leads) |
|