Kyoritsu 2433 Digital Leakage Clamp Meter
Frequency Selector Switch to eliminate the effect of harmonics.
Three AC current ranges : 40mA/400mA/400A.
Data hold function.
Peak hold function.
Sleep function to save battery.
Designed to international safety standard IEC61010-1 CAT.III 300V

Kyoritsu 2433 product photo

 

More Info
Kyoritsu 2433 Product Summary
Kyoritsu 2433 Product Literature
Repair and Calibration Service

 

 
AC A (50/60Hz) 40/400mA/400A
|±1%rdg±5dgt (40/400mA)
|±1%rdg±5dgt (0~350A)
|±2%rdg (350.1~399.9A)
AC A (WIDE)   40/400mA/400A
|±1%rdg±5dgt [50/60Hz],
|±2.5%rdg±10dgt [20Hz~1kHz] (40/400mA)
|±1%rdg±5dgt [50/60Hz],
|±2.5%rdg±10dgt [40Hz~1kHz] (0~350A)
|±2%rdg [50/60Hz],
|±5%rdg [40Hz~1kHz] (350.1~399.9A)
Frequency Response 20Hz~1kHz (40Hz~1kHz:400A)
Maximum Circuit Voltage 600V AC/DC (between line/neutral)
300V AC/DC (against earth)
Conductor Size Ø40mm max.
Safety Standard IEC61010-1 CAT.III 300V Pollution Degree 2
IEC61010-2-032
Effect of External
Stray Magnetic Field
10mA AC approx. in proximity to a 15mm-dia
conductor carrying 100A AC
Withstand Voltage 3700V AC for 1 minute
Response Time Approx. 2 seconds
Power Source Two R03 or equivalent (DC1.5V) batteries
Dimensions 185(L) × 81(W) × 32(D)mm
Weight 270g approx.
Accessories 9052(Carrying Case)
R03(1.5V) × 2
Instruction Manual
Optional 8004/8008(Multi-Tran)*

* These Multi-Trans can not be used for leakage current measurement.

 
 
 
Copyright ©2012 Eaton
Industries Pty Ltd.
All rights reserved.