Continuity Testing |
| Measuring Ranges |
20/200/2000Ω (Autoranging) |
| Open Circuit Voltage |
>6V |
| Short Circuit Current |
>200mA DC |
| Accuracy |
|±(1.5%rdg+3dgt) |
|
Loop Impedance Testing |
| Rated Voltage |
230V AC +10%-15% [50Hz] |
| Voltage Measuring Range |
100~250V AC [50Hz] |
| Impedance Ranges |
20/200/2000Ω |
| Nominal Test Current |
25A (20Ω range)
15mA (200Ω range)
15mA (2000Ω range) |
| Accuracy |
20Ω range ±(3%rdg +4dgt)
200Ω range ±(3%rdg +4dgt)
2000Ω range ±(3%rdg +4dgt) |
|
Insulation Testing |
| Measuring Ranges |
20/200MΩ(Autoranging) |
| Test Voltage |
250V 500V 1000V DC |
Output Voltage on
Open Circuit |
250V+40%-0%
500V+30%-0%
1000V+20%-0% |
| Rated Current |
> 1mA |
| Accuracy |
|±(1.5%rdg+3dgt) |
|
PSC Testing |
| Rated Voltage |
230V AC +10%-15% [50Hz] |
| PSC Ranges |
200A(15mA Test Current)
2000A(25A Test Current)
20kA(25A Test Current) |
| Accuracy |
PSC accuracy derived from
measured loop impedance specification and measured voltage
specification |
|
RCD Testing |
| Rated Voltage |
230V AC +10%-15% [50Hz] |
| Trip Current Settings |
RCD × 1/2 :
10,30,100,300,500,1000mA
RCD × 1 : 10,30,100,300,500,1000mA
RCD × 5 : 10,30,100,300mA (on × 5 ranges max current 1A) |
| Trip Current Duration |
RCD × 1/2 × 1: 2000ms
RCD fast: 50ms |
| Accuracy |
Trip current +10%-0% of
test current at 230V
Trip time ±(1%rdg + 3dgt) |
|
General |
| Safety Standard |
IEC61010-1 CAT.III 300V
Pollution Degree 2
IEC61557 |
| Withstand Voltage |
3700V AC for 1 minute |
| Power Source |
LR6 (1.5V) × 8 |
| Dimensions |
130(L) × 183(W) × 100(D)mm |
| Weight |
1100g approx. |
| Accessories |
*KAPM10
(Molded plug test leads for loop and RCD testing at sockets)
7122(lead for insulation and continuity testing)
KSLP5(external earth probe)
Pouch for Test Leads
Shoulder Strap
Battery LR6 (1.5V) × 8
Instruction Manual |
| Optional Accessories |
OMA DIEC (Distribution
board or lighting circuit test leads for LOOP/PSC/RCD testing) |